Артикул: DL3003 Производитель: IFM

DL3003

Под заказ
RUСклад на Домостроительной 3Д
нет в наличии
CNСклад в Китае
нет предложений
EUСклад в Европе
41 391.30 ₽
срок ≈1 мес. (49 дн.)
ROРумыния
299.29 €
срок ≈1 мес. (49 дн.)

Цены в валюте поставщика с нашей наценкой, без учёта логистики. Самовывоз со склада поставщика за рубежом.

For the reliable limit monitoring of flow, pr

Communication interfaceIO-Link
Housingrectangular
Dimensions [mm]126 x 50 x 112.4
Designhousing for DIN rail mounting
Application2-channel threshold relay for analogue standard signals
Operating voltage [V]110...240 AC / 18...30 DC; (tolerance AC operation: -20 % / +10 %)
Nominal voltage AC [V]110...240
Nominal voltage DC [V]24
Nominal frequency AC [Hz]50...60
Current consumption [mA]AC operation: max. 8 A (including maximum AC supply for additional devices )
Max. power consumption DC [W]9
Overvoltage categoryII
Auxiliary energy for sensors DC [V]16.5...27.7; (Short-circuit proof; DC operation: ≤ 200 mA; AC operation: ≤ 150 mA)
Number of inputs and outputsNumber of analogue inputs: 2; Number of digital outputs: 2; Number of analogue outputs: 1; Number of relay outputs: 2
Number of analogue inputs2; (configurable)
Analogue input (current) [mA]0...20
Input resistance [Ω]300
Analogue input (voltage) [V]0...10
Input resistance [kΩ]25
Resolution12 Bit
Number of digital outputs2
Number of relay outputs2; (changeover contact)
Number of analogue outputs1
CircuitPNP
Max. current load per output [mA]10
Short-circuit proofyes
Electrically separatedyes
Minimum load current [mA]10; (> 12 V)
Contact rating6 A; (max. 240 V AC / 30 V DC see diagram:: Contact rating; B300: 6000 cycles)
Switching frequency AC [Hz]< 2
Switching frequency DC [Hz]< 2
Analogue current output [mA]4...20; (max.. 20,5 mA)
Max. load [Ω]600; (300 Ω: Operating voltage < 24 V DC)
Accuracy± 0.25; (% of the final value < 45 °C; > 45 °C 0.25 % + Temperature coefficient)
Temperature coefficient [% of the span / 10 K]± 0,1; (> 45 °C)
Transmission typeCOM2 (38,4 kBaud)
SDCI standardIEC 61131-9
Required master port typeA
Min. process cycle time [ms]4.9
Supported DeviceIDsType of operation: DeviceID; default: 1583
Ambient temperature [°C]-40...60
Note on ambient temperature110V AC operation: -25...60 °C; 2000...3000 m: max. 58 °C; 3000...4000 m: max. 56 °C; Contact rating relay output: B300 max. 50 °C
Storage temperature [°C]-40...85
Max. relative air humidity [%]80; (31 °C; linearly decreasing to 50 % (40 °C))
Max. height above sea level [m]4000
ProtectionIP 20; (when mounted)
Protection rating terminalsIP 20
Pollution degree2
EMCEN 61000-6-2; EN 61000-6-8
Electrical safetyEN 61010-1; EN 61010-2-201
MTTF [years]150
UL approvalTa: 60 °C; Enclosure type: open Type; File number UL: E191692
Weight [g]338.6
Type of mountingmounting on DIN rail; (TH35 (EN 60715))
Materialshousing: plastics
Display1x OLED display, 128 x 64 pixels luminous; switching status: 2x LED, yellow; operation: 1x LED, green/red
Teach functionyes
Items suppliedcage clamps: 9
RemarksFor information about installation and operation please see the operating instructions.
Pack quantity1 pcs.

Информация об аналогах собирается и скоро появится здесь.

Отгрузка со склада на Домостроительной ул., 3Д (Санкт-Петербург) — в день заказа при наличии товара. Доставка по России транспортными компаниями — обычно 1–7 рабочих дней в зависимости от региона. Точный срок и стоимость доставки рассчитает менеджер при оформлении заявки.

Поставка из-за рубежа (под заказ)

СкладЦенаСрокНаличие
Склад в Европе 41 391.30 ₽ ≈1 мес. (49 дн.) под заказ