Артикул: 2CSR255080R1164
· Производитель: ABB
· EAN: 8012542049210
2CSR255080R1164
В наличии на нашем складе
Наличие в РФ
4 094.00 ₽
в наличии на складе · 124 шт.
Склад в Китае
3 248.60 ₽
срок ≈2 мес. (73 дн.)
Склад в Европе
4 530.20 ₽
срок ≈4 мес. (122 дн.)
The DS201 series is a 1P+N RCBO in two-modules width for the protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct contacts.
Варианты поставки
| Склад | Цена | Срок | Наличие | Мин. партия | |
|---|---|---|---|---|---|
| Склад в Китае | 3 248.60 ₽ | ≈2 мес. (73 дн.) | под заказ | — | Заказать |
| Наш склад | 4 094.00 ₽ | В наличии | 124 шт. | — | Заказать |
| Склад в России | 4 386.69 ₽ | 5 дн. | 1 398 шт. | — | Заказать |
| Склад в Европе | 4 530.20 ₽ | ≈4 мес. (122 дн.) | под заказ | — | Заказать |
| Склад в Европе | 4 727.20 ₽ | ≈2 мес. (66 дн.) | под заказ | — | Заказать |
| Склад в Европе | 4 970.17 ₽ | ≈2 мес. (73 дн.) | под заказ | — | Заказать |
| Склад в Китае | 5 000.87 ₽ | ≈4 мес. (122 дн.) | под заказ | — | Заказать |
| Склад в Европе | 5 003.49 ₽ | ≈2 мес. (73 дн.) | под заказ | — | Заказать |
| Склад в Европе | 5 170.78 ₽ | ≈1 мес. (38 дн.) | под заказ | — | Заказать |
| Склад в Китае | 5 522.62 ₽ | ≈2 мес. (73 дн.) | под заказ | — | Заказать |
| Склад в Китае | 5 615.35 ₽ | ≈1 мес. (45 дн.) | под заказ | — | Заказать |
| Склад в Китае | 5 708.00 ₽ | ≈1 мес. (38 дн.) | под заказ | — | Заказать |
| Склад в Европе | 5 887.24 ₽ | ≈2 нед. (17 дн.) | под заказ | — | Заказать |
| Склад в Европе | 6 361.85 ₽ | ≈1 мес. (59 дн.) | под заказ | — | Заказать |
| Склад в Китае | 7 022.82 ₽ | ≈1 мес. (59 дн.) | под заказ | — | Заказать |
| Склад в Европе | 8 647.64 ₽ | ≈1 мес. (45 дн.) | под заказ | — | Заказать |
| Склад в Европе | 8 956.12 ₽ | уточняется | под заказ | — | Заказать |
| Склад в Китае | 9 546.09 ₽ | ≈1 мес. (45 дн.) | под заказ | — | Заказать |
Характеристики
| Carbon Footprint (Full Lifecycle) | 37.296512 kg CO₂ eq |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 75.20 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill, UL 2799 Zero Waste To Landfill Validation available |
| Sustainable Material Content in Packaging (wt. %) | Recycled Cardboard - 98 %, Recycled Paper - 00 %, Chemically Recycled Polymer - 00 % |
| Extended Product Lifetime | Product Durability |
| Type of Residual Current | Type AC |
| Test Voltage (Ut) | Minimum 170 V, Maximum 264 V |
| Dielectric Test Voltage | 2 kV |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | 10 kA |
| Rated Residual Breaking Capacity (IΔm) | EN 61009-1 6000 A, IEC 61009-1 6000 A |
| Rated Service Short-Circuit Breaking Capacity (Ics) | 7.5 kA |
| Maximum Surge Current | 0 kA |
| Power Supply Connection | Arbitrary |
| Contact Position Indication | Red ON / Green OFF |
| Energy Limiting Class | 3 |
| Electrical Endurance | 10000 cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Protected Poles | 1 |
| Number of Poles | 1P+N |
| Number of Modular Spacings per DIN Rail | 2 |
| Fault Indication | Blue Flag on Toggle |
| Operating Characteristic | Instantaneous |
| Position of Neutral Terminals | Right |
| Tightening Torque | 2.8 N·m |
| Accessory Type | Auxiliary contact, Signal contact / auxiliary contact, Shunt trip, Auxiliary contact for bottom fitting, Overvoltage release, Motor operating device |
| Actuator Type | Toggle |
| Housing Type | Insulation group I - II, RAL 7035 |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Actuator Material | Insulation Group II, Black, Sealable |
| Accessories Available | Yes |
| Number of Batteries | 0 |
| Connecting Capacity | Busbar 10 ... 10 mm², Stranded 0.75 ... 25 mm², Flexible with Ferrule 0.75 ... 16 mm², Flexible 0.75 ... 16 mm² |
| Wire Stripping Length | 12 mm |
| Terminal Type | Screw Terminals |
| Tripping Characteristic | C |
| Rated Operational Voltage | acc. to IEC 60898-1 240 V |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Input Voltage Type | AC |
| Rated Current (In) | 16 A |
| Rated Residual Current | 30 mA |
| Rated Short-Circuit Capacity | 6 kA |
| Rated Conditional Short-Circuit Current (Inc) | 10 kA |
| Rated Frequency (f) | 50 / 60 Hz |
| Power Loss | Average per Pole 2.3 W, Phase Pole 3.4 W, Neutral Pole 1.2 W, Total 4.5 W |
| Overvoltage Category | III |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20211115 |
| REACH Information | True - contains substances > 0.1 mass percentage |
| REACH Date | 20240429 |
| SCIP | 7e384000-93da-4dbd-b496-963b9b48bfa8 Italy |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Consumer |
| Ambient Air Temperature | Operation -25 … 55 °C |
| Reference Ambient Air Temperature | 30 °C |
| Degree of Protection | IP20, IP40 |
| Pollution Degree | 2 |
| Environmental Conditions | 28 cycles, with 55 °C / 90-96 %, and 25 °C / 95-100 % |
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 1g or 0.1mm 5...150...5 Hz |
| Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms |