NFZ contactor relays are used for switching auxiliary and control circuits. NFZ contactor relays include an electronic coil interface accepting a wide control voltage Uc min. ... Uc max. Only four coils cover control voltages between 24...250 V 50/60 Hz or 12...250 V DC. NF contactor relays can manage large control voltage variations. One coil can be used for different control voltages used worldwide without any coil change NFZ contactor relays allow direct control by PLC-output ≥ 24 V DC 500 mA and obtain a reduced holding coil consumption. NFZ contactor relays withstand short voltage dips and voltage sags (SEMI F47-0706 compliance) between 24...250 V 50/60 Hz NFZ contactor relays have built-in surge protection and do not require additional surge suppressors - Poles: 8-pole contactor relays with a non-removable front-mounted auxiliary contact block (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1 and including the "Mechanically Linked" symbol on the contactor relay side) - Control Circuit: DC operated for NF..Z-20 contactors. Only NF..Z-20 contactor relays need to respect the polarity on the coil terminals (A1+ and A2-). - Accessories: a wide range of Accessories is available.

Варианты поставки

СкладЦенаСрокНаличиеМин. партия
Склад в Китае 5 013.43 ₽ ≈2 мес. (73 дн.) под заказ — Заказать
Склад в Китае 5 631.09 ₽ ≈1 мес. (45 дн.) под заказ — Заказать
Склад в Европе 7 183.80 ₽ ≈4 мес. (122 дн.) под заказ — Заказать
Склад в Европе 7 244.11 ₽ ≈1 мес. (38 дн.) под заказ — Заказать
Склад в Европе 7 618.23 ₽ ≈2 мес. (73 дн.) под заказ — Заказать
Склад в Европе 7 805.60 ₽ ≈1 мес. (59 дн.) под заказ — Заказать
Склад в Китае 7 930.17 ₽ ≈4 мес. (122 дн.) под заказ — Заказать
Склад в Китае 7 996.74 ₽ ≈1 мес. (38 дн.) под заказ — Заказать
Склад в Китае 8 522.84 ₽ ≈2 мес. (73 дн.) под заказ — Заказать
Склад в Китае 8 616.57 ₽ ≈1 мес. (59 дн.) под заказ — Заказать
Склад в Европе 8 671.88 ₽ ≈1 мес. (45 дн.) под заказ — Заказать
Склад в Китае 9 572.85 ₽ ≈1 мес. (45 дн.) под заказ — Заказать
Склад в Европе 10 488.16 ₽ уточняется под заказ — Заказать

Характеристики

Minimum Order Quantity1 piece
Customs Tariff Number85364900
Product Net Width45 mm
Product Net Depth / Length110.5 mm
Product Net Height86 mm
Product Net Weight0.36 kg
Number of Auxiliary Contacts NO6
Number of Auxiliary Contacts NC2
Number of Poles8P
StandardsIEC/EN 60947-1, IEC/EN 60947-5-1, UL 60335-2-40 LZGH2 A2L, UL 508, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 14-13
Rated Operational VoltageAuxiliary Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-15 (Ie)(500 V) 2 A, (690 V) 2 A, (24 / 127 V) 6 A, (220 / 240 V) 4 A, (400 / 440 V) 3 A
Rated Operational Current DC-13 (Ie)(24 V) 6 A / 144 W, (48 V) 2.8 A / 134 W, (72 V) 1 A / 72 W, (110 V) 0.55 A / 60 W, (125 V) 0.55 A / 69 W, (220 V) 0.27 A / 60 W, (250 V) 0.27 A / 68 W, (400 V) 0.15 A / 60 W, (500 V) 0.13 A / 65 W, (600 V) 0.1 A / 60 W
Rated Short-time Withstand Current Low Voltage (Icw)for 0.1 s 140 A, for 1 s 100 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-5-1 690 V, acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)6 kV
Maximum Electrical Switching Frequency(AC-15) 1200 cycles per hour, (DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency6000 cycles per hour
Rated Control Circuit Voltage (Uc)DC Operation 12 ... 20 V
Power Lossat 6 A per Pole 0.1 W
Operate TimeBetween Coil De-energization and NC Contact Closing 13 ... 98 ms, Between Coil De-energization and NO Contact Opening 11 ... 95 ms, Between Coil Energization and NC Contact Opening 38 ... 90 ms, Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not supplied)2 x M4 Screws Placed Diagonally
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Rigid Solid 1/2x 1 ... 2.5 mm², Rigid Stranded 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm², Rigid Solid 1/2x 1 ... 2.5 mm², Rigid Stranded 1/2x 1 ... 2.5 mm²
Wire Stripping LengthAuxiliary Circuit 10 mm, Control Circuit 10 mm
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Tightening TorqueAuxiliary Circuit 1.2 N·m, Control Circuit 1.2 N·m
Terminal TypeScrew Terminals
Product NameBlock Contactor Relay
Connecting Capacity Auxiliary Circuit UL/CSARigid Solid 1/2x 18-14 AWG, Rigid Stranded 1/2x 18-14 AWG
Tightening Torque UL/CSAAuxiliary Circuit 11 in·lb, Control Circuit 11 in·lb
Ambient Air TemperatureClose to Contactor for Storage -60 ... +80 °C, Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27Closed, Shock Direction: B1 25 g, Open, Shock Direction: B1 5 g, Shock Direction: A 30 g, Shock Direction: B2 15 g, Shock Direction: C1 25 g, Shock Direction: C2 25 g
Resistance to Vibrations4g Closed Position & 2g Open position 5 ... 300 Hz
Pollution Degree3
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
Improved Energy Efficiency for CustomersProduct Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 92.7 %
Package Level 1 Unitsbox 1 piece
Package Level 1 Width87 mm
Package Level 1 Depth / Length113 mm
Package Level 1 Height47 mm
Package Level 1 Gross Weight0.36 kg
Object Classification CodeK
ETIM 7EC000196 - Contactor relay
ETIM 8EC000196 - Contactor relay
ETIM 9EC000196 - Contactor relay
eClassV11.0 : 27371001
UNSPSC39121529
IDEA Granular Category Code (IGCC)4763 >> Power contactor, DC switching
E-Number (Finland)3706438